Overview
The Moxa MGate MB3660 Series are high-capacity 8 and 16-port redundant Modbus gateways in a 19-inch rackmount form factor. Designed for large-scale SCADA and DCS deployments, they convert between Modbus TCP and Modbus RTU/ASCII, and can be accessed by up to 256 Modbus TCP clients simultaneously. Dual power inputs (AC or DC) and dual Ethernet ports provide redundancy for mission-critical applications including power substations and process plants.
Key Features
- 8 or 16 RS-232/422/485 serial ports (DB9 male, or RJ45 on -J models)
- Accessed by up to 256 Modbus TCP clients; connects to up to 128 Modbus TCP servers
- Innovative Command Learning mode for high-speed SCADA polling performance
- Agent mode: active parallel polling of serial devices, decoupling SCADA from device latency
- Auto Device Routing: single-click slave ID table setup
- Route by TCP port, IP address, or ID mapping for flexible deployment
- Dual 10/100BaseT(X) Ethernet ports — same IP (failover) or dual IPs (simultaneous)
- SD card for configuration backup, duplication, and event logs
- Dual redundant AC or DC power inputs with 1.5 kV DC input isolation
- 2 kV serial port isolation on -I models for power substation applications
- Relay output for power and Ethernet failure alarms
- HTTPS (TLS 1.2), SNMPv3, AES-256, RADIUS authentication
- 19-inch rackmount, 1U form factor, metal housing IP30
- 5-year warranty
High Performance with Command Learning
In transparent mode, the gateway passes Modbus commands between TCP and RTU/ASCII. In agent mode, the gateway actively polls serial devices in parallel, storing responses in local memory so the SCADA system can retrieve data directly without waiting for device round-trip latency — dramatically improving system throughput for large deployments.
Network Redundancy
The dual Ethernet ports can operate with the same IP address for automatic failover between primary and backup LAN, or with separate IP addresses for simultaneous dual-network access by Modbus TCP clients.
Power & Environmental
AC models accept 100–240 VAC; DC models accept 20–60 VDC with 1.5 kV isolation. Both inputs are hot-swappable redundant. Operating temperature is 0 to 60°C for all models. Metal 19-inch rackmount housing (480 x 45 x 198 mm with ears).
Certifications
CE (EN 55032/35), FCC Part 15B Class A, IEC/UL 62368-1, IEC/UL 60950-1 (non-J models). MTBF up to 721,988 hours (Telcordia SR332).