Same day dispatch on all stocked items.
Moxa’s ioLogik E2200 is a new type of Ethernet micro RTU controller, which is a PC-based data acquisition and control device that uses proactive, event-based reporting to control I/O devices. Unlike traditional RTUs, which are passive and must poll for data, Moxa’s ioLogik E2200 series with Active OPC Server makes seamless connection with SCADA systems a reality. In addition, SNMP is used for communicating with an NMS (Network Management System) for IT field users. The I/O status of an Ethernet micro RTU controller can be reported and controlled automatically on-site based on user specified conditions. This report-by-exception approach, which is new to PC-based monitoring, requires far less bandwidth than traditional polling methods.
The ioLogik E2200 Micro RTU supports simple and powerful Click&Go™ technology to deliver event-driven reports and allow alarm messages to be sent by email, TCP/UDP, and SMNP Trap with real-time stamps. With built-in Click&Go™ intelligence, the ioLogik E2200 micro RTU can be used for simple output control when it is triggered by input status, without the need for a PC controller. The ioLogik E2200 micro RTU reports I/O status automatically based on user-specified conditions. This report by-exception approach requires far less bandwidth than the traditional polling approach.
| Inputs and Outputs | |
| Analog Inputs | 4 channels |
| Configurable DI/Os | 12 channels |
| Analog Input | |
| Type | Differential input |
| Resolution | 16 bits |
| I/O Mode | Voltage / Current |
| Input Range | ±150 mV, 0 to 150 mV, ±500 mV, 0 to 500 mV, ±5 V, 0 to 5 V, ±10 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA |
| Accuracy | ±0.1% FSR @ 25°C ±0.3% FSR @ -10 and 60°C ±0.5% FSR @ -40 and 75°C |
| Sampling Rate | All channels: 32 samples/sec Per channel: 8 samples/sec Single channel: 100 samples/sec |
| Input Impedance | 200k ohms (min.) |
| Built-in Resistor for Current Input | 120 ohms |
| Digital Input | |
| Sensor Type | Wet Contact (NPN or PNP) and Dry Contact |
| I/O Mode | DI or event counter |
| Dry Contact | • On: short to GND • Off: Open |
| Wet Contact (DI to GND) | • On: 0 to 3 VDC • Off: 10 to 30 VDC |
| Common Type | 6 points per COM |
| Isolation | 3k VDC or 2k Vrms |
| Counter Frequency | 900 Hz |
| Digital Filtering Time Interval | Software selectable |
| Digital Output | |
| Type | Sink |
| I/O Mode | DO or Pulse Output |
| Pulse Output Frequency | 1 kHz |
| Over-voltage Protection | 45 VDC |
| Over-current Protection | 2.6 A (4 channels @ 650 mA) |
| Over-temperature Shutdown | 175°C (min.) |
| Current Rating | 200 mA per channel |
| Isolation | 3k VDC or 2k Vrms |
| Power Requirements | |
| Power Consumption | 178 mA @ 24 VDC |
| MTBF (mean time between failures) | |
| Time | 204,391 hrs |
| Database | Telcordia (Bellcore) |
| LAN | |
| Ethernet | 1 10/100 Mbps RJ45 port |
| Protection | 1.5 kV magnetic isolation |
| Protocols | Modbus/TCP, TCP/IP, UDP, DHCP, BOOTP, SNMP, HTTP, CGI, SNTP, SMTP |
| Serial Communication | |
| Interface | RS-485-2w: Data+, Data-, GND (3-contact terminal block) |
| Serial Line Protection | 15 kV ESD for all signals |
| Serial Communication Parametres | |
| Parity | None |
| Data Bits | 8 |
| Stop Bits | 1 |
| Flow Control | None |
| Baudrate | 1200 to 115200 bps |
| Protocol | Modbus/RTU |
| Power Requirements | |
| Power Input | 24 VDC nominal, 12 to 36 VDC |
| Physical Characteristics | |
| Wiring | I/O cable max. 14 AWG |
| Dimensions | 115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in) |
| Weight | under 250 g |
| Mounting | DIN rail or wall |
| Environmental Limits | |
| Operating Temperature | Standard Models: -10 to 60°C (14 to 140°F) Wide Temp. Models: -40 to 75°C (-40 to 167°F) |
| Storage Temperature | -40 to 85°C (-40 to 185°F) |
| Ambient Relative Humidity | 5 to 95% (non-condensing) |
| Altitude | Up to 2000 m |
| Note | Please contact Moxa if you require products guaranteed to function properly at higher altitudes. |
| Standards and Certifications | |
| Safety | UL 508 |
| EMI | EN 61000-3-2; EN 61000-3-3; EN 61000-6-4; FCC Part 15, Subpart B, Class A |
| EMS | EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-8, EN 61000-4-11, EN 61000-6-2 |
| Shock | IEC 60068-2-27 |
| Freefall | IEC 60068-2-32 |
| Vibration | IEC 60068-2-6 |
| Green Product | RoHS, CRoHS, WEEE |
| Note | Please check Moxa’s website for the most up-to-date certification status. |
| Warranty | |
| Warranty Period | 5 years (excluding ioLogik E2214*) |
| *Note | Because of the limited lifetime of power relays, products that use that component are covered by a 2-year warranty. |
| Details | See www.moxa.com/warranty |
Same day dispatch on all stocked items.